Pleated Primary
Panel Filter
Pleated polyester media for fresh air, return air and industrial ventilation.
Choose G3 or G4, 45 or 95 mm depth, and one of six face sizes. The pleated medium captures coarse dust and fibres ahead of coils and subsequent filtration stages.
- Filter class
- EN 779 G3 / G4
- Depth options
- 45 / 95 mm
- Medium
- Polyester synthetic fibre
- Frame options
- Metal / plastic
Choose the grade.
Find the right fit.
G3 & G4 options
Two filter grades are available in each depth and face size. Select the grade required by your ventilation system.
Two installation depths
45 mm and 95 mm options accommodate different mounting spaces. Media areas range from 0.2–0.8 m² at 45 mm and 0.4–1.6 m² at 95 mm.
Metal or plastic frames
Choose the frame to match the mounting arrangement and operating environment. Six face sizes include 287 × 287 mm and 592 × 287 mm modules.
Materials & operating parameters
- Filter medium
- Polyester synthetic fibre
- Frame options
- Metal / plastic
- Filter grades
- EN 779 G3 / G4
- Depth options
- 45 / 95 mm
- Listed configurations
- 24
- Face sizes
- 6
- Final pressure drop
- 250 Pa
- Maximum operating temperature
- 80°C
Find your dimensions.
Check your airflow.
Compare six sizes in each grade and depth. Airflow and resistance are listed together at three face velocities.
G3 · 45 mm
| Grade | W × H × D (mm) | Media area (m²) | 1.5 m/s Airflow (m³/h) | 1.5 m/s Resistance (Pa) | 2.5 m/s Airflow (m³/h) | 2.5 m/s Resistance (Pa) | 3.2 m/s Airflow (m³/h) | 3.2 m/s Resistance (Pa) |
|---|---|---|---|---|---|---|---|---|
| G3 | 287×287×45 | 0.2 | 500 | 30 | 850 | 45 | 1000 | 55 |
| G3 | 500×500×45 | 0.6 | 1500 | 30 | 2400 | 45 | 3000 | 55 |
| G3 | 500×625×45 | 0.7 | 1800 | 30 | 2400 | 45 | 3700 | 55 |
| G3 | 592×287×45 | 0.4 | 1000 | 30 | 1750 | 45 | 2100 | 55 |
| G3 | 592×490×45 | 0.6 | 1700 | 30 | 2400 | 45 | 3500 | 55 |
| G3 | 592×592×45 | 0.8 | 2000 | 30 | 3400 | 45 | 4200 | 55 |
G3 · 95 mm
| Grade | W × H × D (mm) | Media area (m²) | 1.5 m/s Airflow (m³/h) | 1.5 m/s Resistance (Pa) | 2.5 m/s Airflow (m³/h) | 2.5 m/s Resistance (Pa) | 3.2 m/s Airflow (m³/h) | 3.2 m/s Resistance (Pa) |
|---|---|---|---|---|---|---|---|---|
| G3 | 287×287×95 | 0.4 | 500 | 25 | 850 | 30 | 1000 | 45 |
| G3 | 500×500×95 | 1.2 | 1500 | 25 | 2400 | 30 | 2900 | 45 |
| G3 | 500×625×95 | 1.4 | 1800 | 25 | 3000 | 30 | 3700 | 45 |
| G3 | 592×287×95 | 0.8 | 1000 | 25 | 1700 | 30 | 2000 | 45 |
| G3 | 592×490×95 | 1.2 | 1700 | 25 | 2800 | 30 | 4000 | 45 |
| G3 | 592×592×95 | 1.6 | 2000 | 25 | 3400 | 30 | 4200 | 45 |
G4 · 45 mm
| Grade | W × H × D (mm) | Media area (m²) | 1.5 m/s Airflow (m³/h) | 1.5 m/s Resistance (Pa) | 2.5 m/s Airflow (m³/h) | 2.5 m/s Resistance (Pa) | 3.2 m/s Airflow (m³/h) | 3.2 m/s Resistance (Pa) |
|---|---|---|---|---|---|---|---|---|
| G4 | 287×287×45 | 0.2 | 500 | 35 | 850 | 50 | 1000 | 60 |
| G4 | 500×500×45 | 0.6 | 1500 | 35 | 2400 | 50 | 2900 | 60 |
| G4 | 500×625×45 | 0.7 | 1800 | 35 | 3000 | 50 | 3700 | 60 |
| G4 | 592×287×45 | 0.4 | 1000 | 35 | 1700 | 50 | 2000 | 60 |
| G4 | 592×490×45 | 0.6 | 1700 | 35 | 2800 | 50 | 4000 | 60 |
| G4 | 592×592×45 | 0.8 | 2000 | 35 | 3400 | 50 | 4200 | 60 |
G4 · 95 mm
| Grade | W × H × D (mm) | Media area (m²) | 1.5 m/s Airflow (m³/h) | 1.5 m/s Resistance (Pa) | 2.5 m/s Airflow (m³/h) | 2.5 m/s Resistance (Pa) | 3.2 m/s Airflow (m³/h) | 3.2 m/s Resistance (Pa) |
|---|---|---|---|---|---|---|---|---|
| G4 | 287×287×95 | 0.4 | 500 | 30 | 850 | 40 | 1000 | 55 |
| G4 | 500×500×95 | 1.2 | 1500 | 30 | 2400 | 40 | 2900 | 55 |
| G4 | 500×625×95 | 1.4 | 1800 | 30 | 3000 | 40 | 3700 | 55 |
| G4 | 592×287×95 | 0.8 | 1000 | 30 | 1700 | 40 | 2000 | 55 |
| G4 | 592×490×95 | 1.2 | 1700 | 30 | 2800 | 40 | 4000 | 55 |
| G4 | 592×592×95 | 1.6 | 2000 | 30 | 3400 | 40 | 4200 | 55 |
Please confirm filter dimensions and operating airflow before ordering.
Dimension guide · schematic, not a manufacturing drawing
Measure the installation.
Confirm the filter.
Measure the existing filter and mounting slot. Include clearances, seals and retaining details.
Provide airflow, allowable pressure drop, temperature and any humidity or liquid exposure.
Share the quantity, required specification and photos or drawings. Non-standard dimensions are reviewed before quotation.
Prefiltration for compatible air systems
Fresh & return air
Coarse-dust and fibre capture in commercial air conditioning and industrial ventilation, ahead of subsequent filtration stages.
Modular air-handling units
Small, half-width and full-width modules support different filter-bank arrangements. Seal the joints between adjacent filters.
Equipment intake & retrofit
Match the existing opening, available depth and airflow. Confirm the frame material and grade before replacing the filter.
Fit correctly. Monitor in service.
Before installation
Confirm dimensions, depth, frame material and airflow direction before installation. Avoid bending the frame or forcing the filter into the opening.
Seat & secure
Apply even retaining pressure and check continuous sealing around the frame. Inspect joints between adjacent filters for bypass gaps.
Track condition
Record the initial pressure drop and compare readings at the same airflow. Inspect media, frame and seals during routine maintenance.
Follow system limits
Replace the filter according to pressure-drop monitoring and equipment maintenance requirements.
Product questions, answered.
Which grades and depths are available?
G3 and G4 are each available in 45 and 95 mm depths, with six face sizes per combination.
How do I choose between 45 and 95 mm?
Check the available mounting depth, then compare the media area, airflow and resistance for the selected grade and size.
Which frame materials can I order?
Metal and plastic frames are available. Include your preferred frame and installation requirements with the enquiry.
What information is needed for a quotation?
Send the required dimensions, grade, depth, frame preference, operating airflow and quantity.
When should the filter be replaced?
Monitor pressure drop and filter condition. The listed final pressure drop is 250 Pa; follow your equipment maintenance requirements.
Send your size.
Let’s confirm the fit.
Tell us the dimensions, quantity and operating requirements. Include photos or drawings in your email so we can review the configuration.