Deep-pleat Separator
HEPA Filters
Aluminium separators. Two depths for your installation.
Deep-pleat HEPA filters with microglass media and corrugated aluminium separators. Select 150 or 292 mm depth, H13 or H14, and a frame configuration for your housing.
- Selected depth
- 150 mm
- Available grades
- H13 / H14
- Frame options
- Aluminium / MDF
- Filter area
- 2.6–10.5 m²
Built around your
installation requirements.
Supported deep-pleat media
Corrugated aluminium separators hold the microglass paper apart to form airflow channels through the filter pack.
Depth-specific frame choices
Choose aluminium or MDF at 150 mm. The 292 mm range offers MDF, galvanized steel or stainless steel.
Gasket and handling options
Both depths use a one-piece foamed polyurethane gasket. The 150 mm model has protective grids, with single- or double-sided grids for MDF frames. Handles are optional on the 292 mm model.
Construction & technical parameters
150 mm configuration
- Filter grades
- H13 / H14
- Frame depth
- 150 mm
- Filter medium
- Microglass fibre
- Separators
- Corrugated aluminium
- Frame options
- Aluminium / MDF
- Recommended final pressure drop
- 600 Pa
- Maximum final pressure drop
- 1000 Pa
- Gasket
- One-piece foamed polyurethane
- Protective grids
- Double-sided epoxy-painted aluminium grids; MDF frames: single- or double-sided
292 mm configuration
- Filter grades
- H13 / H14
- Frame depth
- 292 mm
- Filter medium
- Microglass fibre
- Separators
- Corrugated aluminium
- Frame options
- MDF / galvanized steel / stainless steel
- Recommended final pressure drop
- 600 Pa
- Maximum final pressure drop
- 1000 Pa
- Gasket
- One-piece foamed polyurethane
- Optional accessory
- Handles
Select your filter
configuration.
Choose a grade and select a row to add the dimensions and filter area to your enquiry.
150 mm · H13
| Grade | W × H × D (mm) | Airflow (m³/h) | Initial pressure drop (Pa) | Filter area (m²) | Select |
|---|---|---|---|---|---|
| H13 | 305×305×150 | 325 | 250 | 2.6 | |
| H13 | 457×457×150 | 740 | 250 | 6 | |
| H13 | 305×610×150 | 655 | 250 | 5.2 | |
| H13 | 610×610×150 | 1320 | 250 | 10.5 |
150 mm · H14
| Grade | W × H × D (mm) | Airflow (m³/h) | Initial pressure drop (Pa) | Filter area (m²) | Select |
|---|---|---|---|---|---|
| H14 | 305×305×150 | 325 | 270 | 2.6 | |
| H14 | 457×457×150 | 740 | 270 | 6 | |
| H14 | 305×610×150 | 655 | 270 | 5.2 | |
| H14 | 610×610×150 | 1320 | 270 | 10.5 |
292 mm · H13
| Grade | W × H × D (mm) | Airflow (m³/h) | Initial pressure drop (Pa) | Filter area (m²) | Select |
|---|---|---|---|---|---|
| H13 | 305×305×292 | 450 | 250 | 4.2 | |
| H13 | 457×457×292 | 1000 | 250 | 10 | |
| H13 | 305×610×292 | 900 | 250 | 9 | |
| H13 | 610×610×292 | 1800 | 250 | 18 |
292 mm · H14
| Grade | W × H × D (mm) | Airflow (m³/h) | Initial pressure drop (Pa) | Filter area (m²) | Select |
|---|---|---|---|---|---|
| H14 | 305×305×292 | 450 | 270 | 4.2 | |
| H14 | 457×457×292 | 1000 | 270 | 10 | |
| H14 | 305×610×292 | 900 | 270 | 9 | |
| H14 | 610×610×292 | 1800 | 270 | 18 |
Choose a size below.
Match the housing.
Specify the options.
Dimensions and access
Measure width, height and depth, plus retaining clearance and the route for removing the filter. Provide a housing drawing where available.
Frame and mounting
For 150 mm: aluminium or MDF frame; MDF with single- or double-sided grids. For 292 mm: MDF, galvanized steel or stainless steel frame; optional handles.
Operating conditions
Provide the airflow, available pressure, humidity and operating conditions. Match the sealing face and frame material to your installation.
Applications & system integration
Air-handling units
Select dimensions, airflow and pressure drop against the HEPA stage of the air-handling unit.
Existing-system replacements
Compare the existing frame, sealing face and access space with the selected configuration before ordering.
Clean-air supply systems
Use with upstream prefiltration and a housing designed for the required grade and airflow.
Fit correctly. Monitor in service.
Before installation
Check the frame, media and separators for damage. Carry the filter by its frame and verify airflow direction and housing dimensions.
Seat and secure
Keep the sealing surface clean. Apply retaining pressure evenly around the perimeter and match the gasket arrangement to the housing.
Monitor and replace
Record initial pressure drop at operating airflow and monitor the trend. Recommended final pressure drop: 600 Pa. Maximum final pressure drop: 1000 Pa. Replace earlier if the system requires it.
Product questions, answered.
Which depths and grades are available?
150, 292 mm depths are available in H13 and H14. Select a depth to view its sizes and performance values.
Which frame and mounting options can I order?
For 150 mm: aluminium or MDF frame; MDF with single- or double-sided grids. For 292 mm: MDF, galvanized steel or stainless steel frame; optional handles.
What do I need to measure?
Provide the full width, height and depth in millimetres, plus the mounting interface, sealing face and available removal space.
How do I specify a replacement?
Select a table row and add the quantity, required frame and operating conditions. Include an existing filter label or housing drawing in your email.
When should the filter be replaced?
Monitor pressure drop and the condition of the filter. The recommended final pressure drop is 600 Pa and the maximum is 1000 Pa; your system may require an earlier change.
Send your size.
Let’s confirm the fit.
Tell us the dimensions, quantity and operating requirements. Include photos or drawings in your email so we can review the configuration.